Remark: Do not use for construction. Refer to factory certified dimensions & weights. This page includes data current at time of publication, which should be reconfirmed at the time of purchase. In the interest of product improvement, specifications, weights and dimensions are subject to change without notice.

Last update: 14/12/2024

PCE L122 - L169

PCE_L122_169

1. Fluid in; 2. Fluid out; 3. Overflow; 4. Make up; 5. Drain.

Model Weights (kg) Dimensions (mm) Air Flow (m³/s) Fan Motor (kW) Water Flow (l/s) Pump Motor (kW) R717 charge (kg)
Oper. Weight (kg) Ship. Weight(kg) Heaviest Section (kg) L W H
PCE 122-K-L 4245 3017 2216 2737 2216 3921 16.81 (1x) 7.5 22.0 (1x) 2.2 98.0
PCE 135-L-L 4277 3049 2216 2737 2216 3921 19.08 (1x) 11.0 22.0 (1x) 2.2 98.0
PCE 144-M-L 4286 3058 2216 2737 2216 3921 20.85 (1x) 15.0 22.0 (1x) 2.2 98.0
PCE 136-K-L 4704 3453 2652 2737 2216 4156 16.04 (1x) 7.5 22.0 (1x) 2.2 122.0
PCE 148-L-L 4736 3485 2652 2737 2216 4156 18.17 (1x) 11.0 22.0 (1x) 2.2 122.0
PCE 160-M-L 4745 3494 2652 2737 2216 4156 19.85 (1x) 15.0 22.0 (1x) 2.2 122.0
PCE 143-K-L 5153 3884 3083 2737 2216 4391 15.41 (1x) 7.5 22.0 (1x) 2.2 160.0
PCE 159-L-L 5185 3916 3083 2737 2216 4391 17.43 (1x) 11.0 22.0 (1x) 2.2 160.0
PCE 169-M-L 5194 3925 3083 2737 2216 4391 19.04 (1x) 15.0 22.0 (1x) 2.2 160.0