Remark: Do not use for construction. Refer to factory certified dimensions & weights. This page includes data current at time of publication, which should be reconfirmed at the time of purchase. In the interest of product improvement, specifications, weights and dimensions are subject to change without notice.

General notes

1. Dimensional drawings show standard (right hand) arrangement can be furnished by special order.
2. Coil connection locations are approximate. Dimensions should not be used for prefabrication on the connecting piping. All coil connections are beleved for welding.
3. Shipping/ operating weights indicated are for units without accessories such as sound attenuators, discharge hoods ect. Consult factory certified prints to obtain weight additions and the heaviest section to be lifted. Operating weight shown in tables is based on total unit weight of refrigerant operating charge and basin filled to overflow level.
4. The units will be delivered in 3 different pieces, upper, middle and lower section.

Last update: 03/12/2024

HXC 214-288

HXC_214_288

1. Refrigerant in; 2. Refrigerant out; 3. Make up ND25; 4. Overflow ND80; 5. Drain ND50; 6. Access door.

Model Weights (kg) Dimensions (mm) Air Flow (m³/s) Fan Motor (kW) Water Flow (l/s) Pump Motor (kW) Inlet/Outlet Coil Connections (mm) R717 charge (kg)
Oper. Weight (kg) Ship. Weight(kg) Heaviest Section (kg) L W H Prime Surface Coil Finned Coil Prime Surface Coil Finned Coil
HXC 214 8626 6200 2840 3690 2985 6717 35.13 (2x) 11.0 45.1 (1x) 4.0 kW - 1500RPM (1x) 100 (2x) 100 69.0 16.0
HXC 258 9136 6640 3280 3690 2985 6717 34.7 (2x) 11.0 45.1 (1x) 4.0 kW - 1500RPM (1x) 100 (2x) 100 91.0 16.0
HXC 288 9636 7080 3720 3690 2985 6717 33.74 (2x) 11.0 45.1 (1x) 4.0 kW - 1500RPM (1x) 100 (2x) 100 114.0 16.0
HXC 379 13355 9601 4740 5520 2985 6856 52.89 (3x) 11.0 56.8 (1x) 5.5 kW - 3000RPM (1x) 100 (2x) 100 136.0 24.0
HXC 424 14125 10271 5410 5520 2985 6856 51.4 (3x) 11.0 56.8 (1x) 5.5 kW - 3000RPM (1x) 100 (2x) 100 170.0 24.0