1.0 ICE CHILLER Thermal Storage Unit

1.1 General: The ICE CHILLER® Thermal Storage Unit shall be Baltimore Aircoil Model TSC______. Overall coil dimensions shall not exceed approximately _____ m by ____ m with an overall height not exceeding ____ m. The operating weight shall not exceed _______ kg

1.2 Thermal Capacity: Each coil shall have a thermal storage capacity of _______ kWh operating with ___________refrigerant and a build time of _______ hours at a _______ °C nominal evaporator temperature.

 

2.0 Construction Details

2.1 Coil: The coil shall be constructed of prime surface serpentine steel circuits and shall be tested at 15 bar (31 bar for ammonia applications) air pressure under water. For use with Ammonia refrigerant, the coil shall be complete with purge connection for oil maintenance.

2.2 Ice Thickness Control: A sensing element shall be mounted on the coil to deactivate the refrigerant compressor at a full build of ice.

2.3 Air pump: Centrifugal regenerative blower for field mounting to supply low pressure air for agitation of the water. Pump is complete with a weather protected inlet air filter, and is suitable for outdoor applications.

2.4 Air Distributor: For field mounting. Low pressure air  shall be distributed through multiple perforated PVC pipes.

 