REMARK: Do not use for construction. Refer to factory certified dimensions & weights. This page includes data current at time of publication, which should be reconfirmed at the time of purchase. In the interest of product improvement, specifications, weights and dimensions are subject to change without notice.

General notes

1. Standard refrigerant in- and outlet connection sizes are ND100. Consult your local BAC Balticare representative for locations. Refrigerant connections are closed and coils are filled with an inert gas.
2. Unit height is indicative. For precise value refer to certified print.
3. Shipping/operating weights indicated are for units without accessories such as sound attenuators, discharge hoods, etc. Consult factory certified prints to obtain weight additions and the heaviest section to be lifted. Operating weights shown in the tables is based on total unit weight, weight of refrigerant operating charge and basin filled to overflow level.
4. Drawings show the standard right hand arrangement (air inlet side on the right when facing the connection end). Left hand arrangement can be supplied upon request.


 

Last update: 22/05/2019

PLC xxx-0818E-K

PLC-xxx-0818E-K

1. Refrigerant in ND100; 2. Refrigerant out ND100; 3. Make up ND40; 4. Overflow ND80; 5. Drain ND50; 6. Bleed ND25; 7. Treated water in ND20; 8. Access door.

Model Weights (kg) Dimensions (mm) Air Flow (m³/s) Fan Motor (kW) Water Flow (l/s) Pump Motor (kW) R717 charge (kg)
Oper. Weight (kg) Ship. Weight(kg) Heaviest Section (kg) L W H
PLC 0276-0818E-K 8769 6717 3431 5480 2394 3869 44.92 (4x) 7.0 30.6 (1x) 4.0 150.0
PLC 0317-0818E-K 9684 7584 4298 5480 2394 4104 43.03 (4x) 7.0 30.6 (1x) 4.0 198.0
PLC 0359-0818E-K 10599 8451 5165 5480 2394 4339 41.14 (4x) 7.0 30.6 (1x) 4.0 246.0
PLC 0377-0818E-K 11426 9230 5944 5480 2394 4353 39.25 (4x) 7.0 30.6 (1x) 4.0 294.0
PLC 0403-0818E-K 12321 10077 6791 5480 2394 4544 37.36 (4x) 7.0 30.6 (1x) 4.0 342.0
PLC 0425-0818E-K 13217 10925 7639 5480 2394 4734 35.47 (4x) 7.0 30.6 (1x) 4.0 390.0