REMARK: Do not use for construction. Refer to factory certified dimensions & weights. This page includes data current at time of publication, which should be reconfirmed at the time of purchase. In the interest of product improvement, specifications, weights and dimensions are subject to change without notice.

General notes

1. Standard refrigerant in- and outlet connection sizes are ND100. Consult your local BAC Balticare representative for locations. Refrigerant connections are closed and coils are filled with an inert gas.
2. Unit height is indicative. For precise value refer to certified print.
3. Shipping/operating weights indicated are for units without accessories such as sound attenuators, discharge hoods, etc. Consult factory certified prints to obtain weight additions and the heaviest section to be lifted. Operating weights shown in the tables is based on total unit weight, weight of refrigerant operating charge and basin filled to overflow level.
4. Drawings show the standard right hand arrangement (air inlet side on the right when facing the connection end). Left hand arrangement can be supplied upon request.


 

Last update: 20/04/2019

PLC xxx-0812E-K

PLC-xxx-0812E-K

1. Refrigerant in ND100; 2. Refrigerant out ND100; 3. Make up ND40; 4. Overflow ND80; 5. Drain ND50; 6. Bleed ND25; 7. Treated Water In ND20; 8. Access door.

Model Weights (kg) Dimensions (mm) Air Flow (m³/s) Fan Motor (kW) Water Flow (l/s) Pump Motor (kW) R717 charge (kg)
Oper. Weight (kg) Ship. Weight(kg) Heaviest Section (kg) L W H
PLC 0191-0812E-K 5982 4627 2391 3651 2394 3869 31.65 (3x) 7.0 21.6 (1x) 2.2 100.0
PLC 0218-0812E-K 6600 5214 2978 3651 2394 4104 30.23 (3x) 7.0 21.6 (1x) 2.2 132.0
PLC 0240-0812E-K 7219 5801 3565 3651 2394 4339 28.81 (3x) 7.0 21.6 (1x) 2.2 164.0
PLC 0265-0812E-K 7766 6316 4080 3651 2394 4353 27.4 (3x) 7.0 21.6 (1x) 2.2 196.0
PLC 0282-0812E-K 8371 6889 4653 3651 2394 4544 25.98 (3x) 7.0 21.6 (1x) 2.2 228.0
PLC 0294-0812E-K 8976 7462 5226 3651 2394 4734 24.56 (3x) 7.0 21.6 (1x) 2.2 260.0