REMARK: Do not use for construction. Refer to factory certified dimensions & weights. This page includes data current at time of publication, which should be reconfirmed at the time of purchase. In the interest of product improvement, specifications, weights and dimensions are subject to change without notice.

General notes

1. Adiabatic cooler capacities are tested according to EN 1048 for dry coolers.
2. TrilliumSeries Coolers of models with D6xx coil configuration have inlet and outlet connections at opposite ends.
3. Adiabatic pre-cooling sections are shipped separately and need to be installed on site.

Last update: 23/03/2019

DFCV-AD Q/S 9123

DFCV-AD Q91XX

1. Fluid inlet connection; 2. Fluid outlet connection; 3. Pre-cooler water drain; 4. Electrical panel; 5. Pre-cooler city water connection.

Model Nr. of Fans Weights (kg) Dimensions (mm) Air Flow (m³/s) Tube Internal Volume (dm³) Surface (m²) Connections
Oper. Weight (kg) Ship. Weight(kg) Heaviest Section (kg) L W H Δ
DFCV Q9123-D613-D-AD 6 2580 2350 2030 4081 2730 2810 16.8 272.0 2232.0 4
DFCV Q9123-L613-D-AD 6 2580 2350 2030 4081 2730 2810 16.8 272.0 2232.0 4
DFCV Q9123-M613-D-AD 6 2580 2350 2030 4081 2730 2810 16.8 272.0 2232.0 4
DFCV Q9123-S613-D-AD 6 2580 2350 2030 4081 2730 2810 16.8 272.0 2232.0 4
DFCV S9123-D613-D-AD 6 2334 1948 1794 4081 2730 2810 31.8 272.0 2232.0 4
DFCV S9123-D616-D-AD 6 2666 2120 1967 4081 2730 2810 33.0 432.0 2000.0 4
DFCV S9123-L613-D-AD 6 2334 1948 1794 4081 2730 2810 31.8 272.0 2232.0 4
DFCV S9123-L616-D-AD 6 2666 2120 1967 4081 2730 2810 33.0 432.0 2000.0 4
DFCV S9123-M613-D-AD 6 2334 1948 1794 4081 2730 2810 31.8 272.0 2232.0 4
DFCV S9123-M616-D-AD 6 2666 2120 1967 4081 2730 2810 33.0 432.0 2000.0 4
DFCV S9123-S613-D-AD 6 2334 1948 1794 4081 2730 2810 31.8 272.0 2232.0 4
DFCV S9123-S616-D-AD 6 2666 2120 1967 4081 2730 2810 33.0 432.0 2000.0 4