REMARK: Do not use for construction. Refer to factory certified dimensions & weights. This page includes data current at time of publication, which should be reconfirmed at the time of purchase. In the interest of product improvement, specifications, weights and dimensions are subject to change without notice.

General notes

1. Sound Pressure Levels (LpA) are measured in the horizontal plane at a distance of 10 m from the connection end of the unit, under free field conditions.
2. Adiabatic pre-cooling sections are shipped separately and need to be installed on site.

Last update: 17/07/2019

DCV-AD S9122-S416

DCV-AD S9122-S416

1. Refrigerant inlet connections; 2. Refrigerant outlet connections; 3 . Pre-cooler water drain and overflow; 4. Electrical panel; 5. Pre-cooler city water connection.

Model Nr. of Fans Air Flow (m³/s) Surface (m²) Tube Internal Volume (dm³) LpA dB(A) Ship. Weight(kg) Dimensions (mm)
Δ /ϒ Δ /ϒ L W H
S9122-S416D-AD 4 (2+2) 24/18 1850 191 59/52 1557 2931 2730 2810
S9123-S416D-AD 6 (3+3) 36/27 2775 287 61/54 2190 4081 2730 2810
S9124-S416D-AD 8 (4+4) 48/35,9 3700 382 61/54 2871 5181 2730 2810
S9125-S416D-AD 10 (5+5) 60/44,9 4625 478 62/55 3564 6313 2730 2810
S9126-S416D-AD 12 (6+6) 72/53,9 5550 574 63/56 4218 7413 2730 2810